0.6/1kV CU/XLPE/ OA.SCR/LSZH/SWA/LSZH Power Cable
For used in power transmission and distribution system. suitable for outdoor use at temperature range
from -52℃ to +80℃. For VSD system application.
3.1 Conductor
Up to 25mm²: Plain annealed stranded circular non-compacted
copper conductor in accordance with IEC 60228 Class 2
Above 25mm²: Plain annealed stranded circular compacted copper
conductor in accordance with IEC 60228 Class 2
3.2 Insulation
Extruded XLPE compound comply with IEC 60502-1
Color:
3C: Black, Brown, Grey
3.3 Earth conductor
Three earth insulation conductors (color: Yellow/Green) arranged in
360°symmetrical configuration
3.4 Assembly and filler(optional)
The interstices between cores filled with non-hygroscopic
polypropylene rope to form substantially circular shape with a
suitable binder tape
3.5 Metallic Screen
A layer of copper tape helically overlap applied on the assembly
core
3.6 Separation sheath
Extruded LSZH ST8 compound comply with IEC 60502-1
Color: Black
3.7 Metal amour
A layer of galvanize steel wires with suitable binder tape helically
applied on the separation sheath
3.8 Outer sheath
Extruded LSZH ST8 compound comply with IEC 60502-1
Color: Black
For example:
EAC YANGER® IEC 60332-3-22 CU/XLPE/OA.SCR/LSZH/SWA/LSZH 3C×SIZE+3E×SIZE SQMM 0.6/1kV нг (А) – HF
-52°C~+40°C 2020 ****M
Note: “****M” meter marking by inkjet with increased sequence with numbering
“нг (А) – HF” at least every 1 metre appear on the cable
Rated voltage, U0/U(Um), kV | 0.6/1(1.2) |
Rated, operating temperature range, ℃ | -52~+80 |
Min. installation temperature without preheating, ℃ | -20 |
Max. conductor temperature in service, ℃ | 90 |
Max. permissible short-circuit temperature,5 sec, ℃ | 250 |
Min. bending radius, D overall diameter of cable | 15D |
Flame retardant | IEC 60332-3-22 |
Halogen Gas Emission | IEC 60754-1, < 0.5% |
Low Smoke Emission | IEC 61034-1/2 |
UV resistant | UL 1581 |
Oil resistant | IEC60811(IRM 902 – 4h at 70°C,variation ±40%) |
Oxygen Index(Sheath) | ASTM D 2863 |
Cold bend | IEC 60811-1-4, -35℃ |
Cold impact | IEC 60811-1-4 & CSA C22.2 No.38-10, -35℃ |
Chemical resistance | Accidental |