0.6/1kV CU/XLPE/LSZH Power Cable

Short Description:

For used in power transmission and distribution system. suitable for outdoor use at temperature range from -52℃ to +80℃.


  • Application: For used in power transmission and distribution system. suitable for outdoor use at temperature range from -52℃ to +80℃.
  • Standard & specification: Cable design comply with IEC 60502-1, IEC 60228, GOST 31996- 2012, GOST 22483-2012, IEC 60332-3-22, IEC 61034, IEC 60754-2
  • RFQ

    Product Detail

    Design

    Cable marking-Inkjet

    Operation condition

    Product Tags

    For used in power transmission and distribution system. suitable for outdoor use at temperature range from -52℃ to +80℃.


  • Previous:
  • Next:

  • 3.1 Conductor

    Up to 2.5mm²: Tinned annealed stranded circular non-compacted
    copper conductor in accordance with IEC 60228 Class 2
    4 to 25mm²: Plain annealed stranded circular non-compacted
    copper conductor in accordance with IEC 60228 Class 2
    Above 25mm²: Plain annealed stranded circular compacted copper
    conductor in accordance with IEC 60228 Class 2

    3.2 Insulation

    Extruded XLPE compound comply with IEC 60502-1
    Color:
    2C: Brown, Blue
    3C: Black, Brown, Grey
    4C: Black, Brown, Grey, Blue
    2C+E: Brown, Blue, Green/Yellow (Earth)
    3C+E: Black, Brown, Grey, Green/Yellow (Earth)
    4C+E: Black, Brown, Grey, Blue, Green/Yellow (Earth)
    5 core and above: black core printed white numbers

    3.3 Assembly and filler(optional)

    The interstices between cores filled with non-hygroscopic
    polypropylene rope to form substantially circular shape with a
    suitable binder tape

    3.4 Outer sheath

    Extruded LSZH ST8 compound comply with IEC 60502-1
    Color: Black

    For example:
    EAC YANGER® IEC 60332-3-22 CU/XLPE/LSZH 2C×2.5+E 2.5 SQMM 0.6/1kV нг (А) – HF -52°C~+40°C
    YEAR ****M
    Note: “****M” meter marking by inkjet with increased sequence with numbering
    “нг (А) – HF” at least every 1 metre appear on the cable

    Rated voltage, U0/U(Um), kV 0.6/1(1.2)
    Rated, operating temperature range, ℃ -52~+80
    Min. installation temperature without preheating, ℃ -20
    Max. conductor temperature in service, ℃ 90
    Max. permissible short-circuit temperature,5 sec, ℃ 250
    Min. bending radius, D overall diameter of cable 15D
    Flame retardant IEC 60332-3-22
    Halogen Gas Emission IEC 60754-1, < 0.5%
    Low Smoke Emission IEC 61034-1/2
    UV resistant UL 1581
    Oil resistant IEC60811(IRM 902 – 4h at 70°C, variation ±40%)
    Oxygen Index(Sheath) ASTM D 2863
    Cold bend IEC 60811-1-4, -35℃
    Cold impact IEC 60811-1-4 & CSA C22.2 No.38-10, -35℃
    Chemical resistance Accidental
  • Write your message here and send it to us