0.6/1kV CU/XLPE/LSZH Earthing Cable

Short Description:

For used in light fitting, and in switching and control equipment. suitable for outdoor use at temperature
range from -52℃ to +80℃.


  • Application: For used in light fitting, and in switching and control equipment. suitable for outdoor use at temperature range from -52℃ to +80℃.
  • Standard & specification: Cable design comply with IEC 60502-1, IEC 60228, GOST 31996- 2012, GOST 22483-2012, IEC 60332-3-22, IEC 61034, IEC 60754-2
  • RFQ

    Product Detail

    Design

    Cable marking-Inkjet

    Operation condition

    Product Tags

    For used in light fitting, and in switching and control equipment. suitable for outdoor use at temperature
    range from -52℃ to +80℃.


  • Previous:
  • Next:

  • 3.1 Conductor
    Up to 25mm²: Plain annealed stranded circular non-compacted
    copper conductor in accordance with IEC 60228 Class 2
    Above 25mm²: Plain annealed stranded circular compacted copper
    conductor in accordance with IEC 60228 Class 2
    3.2 Insulation
    Extruded XLPE compound comply with IEC 60502-1
    Color: Natural
    3.3 Binder Tape
    Non-hygroscopic tape wrapped around the insulated core
    3.4 Outer sheath
    Extruded LSZH ST8 compound comply with IEC 60502-1
    Color: Yellow with a green strip

    For example:
    EAC YANGER® IEC 60332-3-22 CU/XLPE/LSZH 1C×16 SQMM 0.6/1kV нг (А) – HF -52°C~+40°C 2020 ****M
    Note: “****M” meter marking by inkjet with increased sequence with numbering
    “нг (А) – HF” at least every 1 metre appear on the cable

    Rated voltage, U0/U(Um), kV 0.6/1(1.2)
    Rated, operating temperature range, ℃ -52~+80
    Min. installation temperature without preheating, ℃ -20
    Max. conductor temperature in service, ℃ 90
    Max. permissible short-circuit temperature,5 sec, ℃ 250
    Min. bending radius, D overall diameter of cable 20D
    Flame retardant IEC 60332-3-22
    Halogen Gas Emission IEC 60754-1, < 0.5%
    Low Smoke Emission IEC 61034-1/2
    UV resistant UL 1581
    Oil resistant IEC60811(IRM 902 – 4h at 70°C, variation ±40%)
    Oxygen Index(Sheath) ASTM D 2863
    Cold bend IEC 60811-1-4, -35℃
    Cold impact IEC 60811-1-4 & CSA C22.2 No.38-10, -35℃
    Chemical resistance Accidental