Ship shore power composite cable
The cable which Yanger offered shall be designed, manufactured and tested according to international standards as follows:
IEC 60228 |
Conductors of insulated cables |
IEC 60092-350 | Shipboard power cables general construction and test requirements |
IEC 60092-360 | Insulating and sheathing materials for shipboard and offshore units.Power, control, instrumentation and telecommunication cables |
EN 50363-10-2 | Insulating, sheathing and covering materials for low voltage energy cablesPart 10-2: Miscellaneous sheathing compounds – Thermoplasticpolyurethane |
Cable Structure
Type: GEUR 0.6/1kV 3×185+2×50+4×2.5
Note: The above drawing is only for reference
3.1.2 Voltage: 0.6/1kV
3.1.3 Bend radius: ≥6D
3.1.4 Operating ambient temperature: -25℃~+70℃
3.1.5 Max. permissible continuous operating temperature of conductor: 90℃
3.1.6 Standard
3.1.6.1 Conductor: IEC 60228
3.1.6.2 Insulation: IEC 60092-360
3.1.6.3 Sheath: EN 50363-10-2
3.1.7 Structure
3.1.7.1 Phase cores conductor: Tinned copper(Class 5)
3.1.7.2 Phase cores insulation: EPR
3.1.7.3 Grounding cores conductor: Tinned copper(Class 5)
3.1.7.4 Grounding cores insulation: EPR
3.1.7.5 Ground check cores conductor: Tinned copper(Class 5)
3.1.7.6 Ground check cores insulation: EPR
3.1.7.7 Ground check cores screen: Tinned copper braided
3.1.7.8 Inner sheath: TPU
3.1.7.9 Strength layer: Ripcord braided
3.1.7.10 Outer sheath: TPU
3.1.8 Color of Sheath and Insulation Identification
3.1.8.1 Power cores identification: Brown, Black, Grey
3.1.8.2 Earth wire identification: Yellow/Green
3.1.8.3 Pilot cores identification: Black
3.1.8.4 Sheath color: Black
3.1.9 Mark: ZTT GEUR 0.6/1kV Size 90°C IEC 60092-353 Serial No.
Meter mark
3.1.10 Dimension Date
3.1.10.1 Maximum outer diameter: 68.0mm
3.1.10.2 Approx. weight: 10083kg/km
3.1.10.3 Max. tensile load: 11100N
3.1.10.4 Reference current-carrying capacity for
phase cores (45℃ ambient temperature): 311A