0.6/1kV CU/XLPE/LSZH/SWA/LSZH Instrument Power Cable
For used in power transmission and distribution system, suitable for outdoor use at temperature range
from -52℃ to +80℃.
3.1 Conductor
Plain annealed stranded circular copper conductor in accordance
with IEC 60228 Class 2
3.2 Insulation
Extruded XLPE compound comply with IEC 60502-1
Color:
Pair: Brown, Grey
3G: Brown, Light Blue, Green/Yellow (Earth)
5G and above: black core printed white numbers and Green/Yellow
(Earth)
3.3 Assembly and filler(optional)
The interstices between cores filled with non-hygroscopic
polypropylene rope to form substantially circular shape with a
suitable binder tape
3.4 Inner sheath
Extruded LSZH ST8 compound comply with IEC 60502-1
Color: Black
3.5 Metal amour
A layer of galvanize steel wires with suitable binder tape helically
applied on the inner sheath
3.6 Outer sheath
Extruded LSZH ST8 compound comply with IEC 60502-1
Color: Black
For example:
EAC YANGER® IEC 60332-3-22 CU/XLPE/LSZH/SWA/LSZH 3G×2.5 SQMM 0.6/1kV нг (А) – HF Project Cable Code
-52°C~+40°C YEAR ****M
Note: “****M” meter marking by inkjet with increased sequence with numbering
“нг (А) – HF” at least every 1 metre appear on the cable
Rated voltage, U0/U(Um), kV | 0.6/1(1.2) |
Rated, operating temperature range, ℃ | -52~+80 |
Min. installation temperature without preheating, ℃ | -30 |
Max. conductor temperature in service, ℃ | 90 |
Max. permissible short-circuit temperature,5 sec, ℃ | 250 |
Min. bending radius, D overall diameter of cable | 15D |
Flame retardant | IEC 60332-3-22 |
Halogen Gas Emission | IEC 60754-1, < 0.5% |
Low Smoke Emission | IEC 61034-1/2 |
UV resistant | UL 1581 |
Oil resistant | IEC60811(IRM 902 – 4h at 70°C,variation ±40%) |
Oxygen Index(Sheath) | ASTM D 2863 |
Cold bend | IEC 60811-1-4, -52℃ |
Cold impact | IEC 60811-1-4 & CSA C22.2 No.38-10, -52℃ |
Chemical resistance | Accidental |